Series 90-30 DeviceNet Slave Module
by Sebastian Seow
Summary
GE Fanuc is pleased to introduce the Series 90-30 DeviceNet Slave Module, IC693DNS201. This module provides the Series 90-30 the capability of a DeviceNet Conformance Tested DeviceNet slave.
The Module allows the Series 90-30 to be a slave on a DeviceNet Fieldbus and to pass up to 255 bytes of inputs to the Master and receive up to 255 bytes of outputs from the master.
Features/Description
The IC693DNS201 DeviceNet Slave module provides the Series 90-30 the capability to be a slave on DeviceNet network(s). The module is DeviceNet Conformance Tested and conforms to DeviceNet specifications. The DeviceNet Data Rates (125K, 250K, and 500 Baud) are supported. The Module can have up to 255 bytes of input data and up to 255 bytes of output data. DeviceNet compliant Status LEDs for ¡°Module Status¡± and ¡°Network Status ¡± are provided, in addition a ¡°Network Power¡± LED is provided.
The following status information is available for the DeviceNet slave:
- Slave Status Word
- Firmware Module Revision
- COMMREQ to Read Module Header
A RS232 service port is provided for firmware updates.
Compatibility
- All current models of Series 90-30 CPUs with revision of 8.00 or higher will support the DeviceNet Slave.
- CIMPLICITY Machine Edition Logic Developer Version 3.00 is required to configure the DeviceNet Slave Module. The DeviceNet Slave is not supported byVersaPro and Logicmaster.
- The DeviceNet Slave Module can go in any I/O slot in a Main Rack, Expansion Rack, or Remote Rack (Note: performance will be decrease in Remote Racks).
Module Specifications
|
DeviceNet |
|
|
Standard Compliance |
DeviceNet Specification Version 2 |
|
Certification |
DeviceNet Conformance Tested |
|
Data Rates |
125K, 250K, 500K Baud |
|
Data Capacity |
255 bytes in, 255 bytes out |
|
UCMM capable Group2 server |
Up to 250 simultaneous explicit messaging connections |
|
Poll mode IO |
Supported |
|
Strobe mode IO |
Supported |
|
Cyclic mode IO |
Supported |
|
Change of State I/O |
Supported |
|
Explicit Messaging |
Supported |
|
CAN Buffers |
Maximum of 512 in queue |
|
|
|
|
Hardware |
|
|
Parameter and Diagnostic Memory |
12K bytes |
|
Operating Temperature |
0 C to 60C |
|
Storage Temperature |
-40 C to 85 C |
|
Backplane Power Consumption |
450 mA @ 5VDC (typical) |
|
LEDs |
3 LEDs ¡°Module Status¡±, ¡°Network Status¡± and ¡°Network Power¡± (dual color Red/Green) |
|
DeviceNet Port |
5 Pin DeviceNet removable screw terminal connector |
|
Service Port |
9 Pin male D-shell connector (RS232), used for firmware updates |
|
Compatibility |
|
|
Programmer |
Requires CIMPLICITY Machine Edition Logic Developer Version 3.0 or later |
|
PLC CPU |
Any CPU Revision 8.0 or higher (321 and 340 not supported) |
|
Module location |
Any I/O slot in: Main Rack, Expansion rack, Remote Rack |
Ordering Information
|
Catalog Number |
Description |
|
IC693DNS201 |
DeviceNet Slave Module |
The Series 90-30 DeviceNet Slave is open for orders
Related Documentation
GFK-2197 User¡¯s Manual
9030Slave.eds EDS File
Sebastian Seow
Marketing Manager
Phone: (0065) 6899 5144
Fax: (0065) 6566 7409
E-mail: Sebastian.seow@gefanucasia.ge.com
Series 90 is a trademark of GE Fanuc Automation North America, Inc.
DeviceNet is a trademark of ODVA