Introduction

Do you ever wish that you could put your serial PLCs and Operator Interfaces on Ethernet?  Got old PLC's installed that you're communicating to via serial cables when you've got Ethernet installed everywhere?  Tired of walking out to the plant floor with a programming unit to connect up to a PLC serially to change or monitor a program?  No matter what brand PLC or Operator Interface you are using, GE Fanuc's VersaMaxTM SE (Serial-Ethernet converter) is just what you need to take advantage of the Ethernet network you have installed in your plant.

Product Summary

GE Fanuc Automation's VersaMax SE (IC200SET001) is a versatile, cost-effective programmable logic controller accessory that enables Ethernet connection via the serial port on the controller. The new VersaMax SE complements the VersaMax Nano and VersaMax Micro controllers, as well as any other GE Fanuc PLC that has a serial interface. The VersaMax SE allows users to solicit and send information, upload/download programs, and monitor and control devices over Ethernet.

The VersaMax SE (IC200SET001) is packaged with a pre-made four inch RJ-45 to RJ-45 cable, that goes from the VersaMax Micro or Nano to the VersaMax SE, manual and utility disk. As with the VersaMax Micro and Nano controllers, the VersaMax SE accessory features the convenience of DIN rail mounting, allowing users to install the product onto a DIN rail rack and attach the serial interface of the device to the VersaMax SE.

Click HERE to download the VersaMax SE Datasheet (PDF format, 143K)

Specifications:

Topic

Description

Part Number- IC200SET001

Ethernet to Serial Interface module

Operating Temperature

0 to 60C

Dimensions

90 x 60 x 36 mm

Mounting

DIN Rail only

Power Requirement

9 VDC to 30 VDC max. 3 watts

Agency Certification

UL, CE, FCC, CUL, TUV and FM pending

Serial Port

 

Serial Communications Port

(Switch selectable RS-232 or RS-485)

RS-232 (RJ45) or

RS-232 or RS-485 screw block connection (Upto 16 drops supported in RS-485 mode. SNP does not support multidrop through VersaMax SE, point to point only.)

Serial Baud Rates

300 to 38400 bps (19.2Kbs factory default)

Serial Protocols

SNP (factory default)

Modbus RTU

ASCII

Network Interface

 

Connection Type

RJ45 (10BASET Connector)

Transmission Speed

10 Mbit Ethernet

Hardware Address

The first three bytes are fixed, and read 00-20-4A,. The forth, fifth, and sixth bytes represents the type of product and serial number in Hex notation.

IP Protocols

SRTP with limited EGD (factory default)

Modbus Ethernet TCP/IP

UDP

TCP

Telnet

Configuration Tools

 

Setup Software

Telnet or SNMP over the network or via the serial port

The VersaMax SE includes screw terminal blocks that support RS-232 or RS-485 serial interfaces or an RJ45 connector supporting the RS-232 standard for serial device attachment. Serial speeds of up to 38.4 Kbps are supported along with DSR and DTR modem controls. In terms of networking, the VersaMax SE supports an RJ45 10BASE-T interface at 10 Mb that allows convenient Ethernet network access.

Once connected to the network, the VersaMax SE allows users to choose from a wide range of IP protocols. The VersaMax SE is pre-configured with SNP (Series Ninety Protocol) on the serial side and SRTP (GE Fanuc Ethernet) on the Ethernet side with limited Ethernet Global Data (EGD) support. Additional IP protocols supported are Modbus Ethernet, UDP, TCP, and Telnet and on the serial side Modbus RTU and ASCII.

The multi-protocol options of the VersaMax SE provide customizable support for PLCs, printers, bar code readers, variable frequency drives, solid-state starters, or other ASCII devices that require Ethernet connection.

Additionally, the VersaMax SE provides a wealth of management options for controlling attached serial devices. It can be managed via Telnet or SNMP over the network and configured or managed via its serial port. It also contains Flash ROM that allows new or customized versions of operating code to be easily downloaded from the TCP/IP host (TFTP download) or via the serial port.

VersaMax SE Configuration and Support Matrix

VersaMax SE Serial Port

VersaMax SE Ethernet Port

Product Supported

Functionality

SNP

SRTP

SNP supported devices. VersaMax Micro, Nano, Modular, Series 90Ô Micro, Series 90-30, Series 90-70

Support for VersaPro, OPC SRTP servers, CIMPLICITY HMI

Modbus RTU

Modbus Ethernet

Modbus RTU Slave supported devices. VersaMax Micro, Nano, Modular, Series 90 Micro, Series 90-30, Series 90-70, Series 5, Series 6, GE Drives, OCS, etc

Support for OPC Modbus Ethernet server, CIMPLICITY HMI

Character Pass through mode

Character Pass through mode

Any serial protocol without close timing tollerance. Requires a VersaMax SE on both ends.

Replaces serial wire with Ethernet cable.

The following illustrations highlight just a few ways you can use the VersaMax SE to leverage your investment in your ethernet network.

 

 

For information on the VersaMax SE, please contact your local GE Fanuc Authorized distributor.

VersaMax, VersaPro, Logicmaster are trademarks and CIMPLICITY is a registered trademark of GE Fanuc Automation.


[PRINTER FRIENDLY VERSION]
Published by Alicia Bowers
Copyright © 2001 GE Fanuc Automation. All rights reserved.
New Page 1

GE Fanuc Automation Information Centers

  • USA & Canada 1 800 648-2001
  • Mexico & Latin America 434-978-5100
  • Europe, Africa & Mid East (352) 727979-1
  • Asia Pacific 65-566-4918

Internet:  http://www.gefanuc.com    We welcome your feedback

TELL A FRIEND
View Archive
Powered by iMakeNews.com